BRANCH CIRCUITS
- In
no case shall the total load exceed the branch-circuit ampere rating
nor the max. loads
specified in NEC sections 220-4.
- An individual branch
circuit shall be permitted to supply any load for which it is rated.
- Branch-circuit conductors
shall have an ampacity not less than the max. load to be served.
- Branch-circuit
conductors supplying household ranges, wall-mounted ovens, counter-mounted
cooking
units, and other household cooking appliances shall have an
ampacity not less than the rating of the branch circuit and not less
than the max. load to be served. 210-19(c).
- For
ranges of 8 3/4 kw or more rating, the min. branch-circuit rating shall
be 40 amperes.
210-19(c).
- A min. 40-amperes branch-circuit
rating would be as follows:
No. 8 AWG copper, Type TW= 40 Amps, OR
No. 6 AWG aluminum, Type TW= 40 Amps
See NEC, Table 210-24 for other applications. There are other
exceptions- see 210-19(c).
- Arc-Fault
Circuit Interrupters, NEC 210-12: All branch circuits that supply 125-volt,
15 and 20-ampere outlets installed in dwelling unit
bedrooms shall be protected by an Arc-Fault Circuit Interrupter(s),
(AFCI).
- Calculating
the number of 15 and 20-ampere branch circuits that are needed in a
single family dwelling:
see
example.
- What
does "14-2" mean?
- Cables
Marking.
- Conductors
Identification.
- Jump
to
Application & Wiring
Guide.
- See
simple
light circuits diagrams.
- Three-way
switches diagram.
- Switch-controlled
receptacles.
- For
multi-conductor cables,
see
sketch.
- See
receptacles and GFCI-receptacles
sketch.
- Switches:
the
different kinds available.
- Electrical
boxes.
- Electrical
boxes fill calculations.
- A branch circuit supplying
two or more outlets or receptacles shall supply only the loads according
to its size- see table below:
Summary of
Branch-Circuit Requirements
|
Circuit
Rating
|
15
Amp
|
20
Amp
|
30
Amp
|
40
Amp
|
50
Amp
|
Conductors:
(Min. size)
Circuit Wires*
|
14
|
12
|
10
|
8
|
6
|
Taps
|
14
|
14
|
14
|
12
|
12
|
Fixture
Wires & Cords
|
|
|
|
See
NEC section 240-4
|
|
Overcurrent
Protection
|
15
Amp
|
20
Amp
|
30
Amp
|
40
Amp
|
50
Amp
|
Outlet
Devices:
Lampholders Permitted
|
Any Type
|
Any Type
|
Heavy Duty
|
Heavy Duty
|
Heavy Duty
|
Receptacle
Rating**
|
15 Amps.
max.
|
15 or 20
Amps
|
30 Amps
|
40 or 50
Amps
|
50 Amps
|
Max. cord-and
Plug connected load to Receptacle
|
12 Amps
|
16 Amps
|
24 Amps
|
-
|
-
|
MAX.
Load
|
15
Amp
|
20
Amp
|
30
Amp
|
40
Amp
|
50
Amp
|
Permissible
Load
|
See NEC
section 210-23(a)
|
See NEC
section 210-23(a)
|
See NEC
section 210-23(b)
|
See NEC
section 210-23(c)
|
See NEC
section 210-23(c, d)
|
* Gauges are for copper
conductors
** For receptacles rating of cord-connected electric discharge
lighting fixtures, see NEC section 410-30(c)
|
|