GENERAL
PURPOSE CIRCUITS
Receptacles-
where required
- Where
needed, NEC 210-52(a): Receptacle outlets are needed at any wall
equal
or more than 2 ft. in width. ,
- Receptacles
Spacing, NEC 210-52(a): Receptacles shall be so spaced that a 6
ft.
cord can be plugged anywhere along the wall. ,
- Receptacle Outlets
in the Floor, NEC 210-52(a): Can be counted as part of the required
number of outlets provided they are within 18" of the wall.
- Receptacles
at Front & Back, NEC 210-52(e): Need at least one receptacle
outlet, accessible at grade level and within 6 ft. 6 inches above
grade (GFCI
& waterproof-protected), at the front and back of the dwelling. ,
- Receptacles
in Bathrooms, NEC 210-52(d): Need at least one wall receptacle outlet,
GFCI-protected, adjacent to each basin in every bathroom.
Where the basins are in close proximity, one outlet can be installed
between the two basins.
- Receptacles
in Laundry Rooms, NEC 210-52(f): Need at least one receptacle
outlet. The branch circuit serving the outlet shall be min. 20-amp
rated and without any other loading from lights and outlets.
- Receptacles
in Garages & Basements, NEC 210-52(g): Need at least one receptacle
outlet (GFCI-protected). ,
- Arc-Fault
Circuit Interrupters, NEC 210.12: All branch circuits that
supply 125-volt, 15 and 20-ampere outlets (lights, smoke detectors,
receptacle outlets, etc) installed in dwelling unit bedrooms
shall be protected by an Arc-Fault Circuit Interrupter(s), (AFCI).
- Receptacle
Outlets for Servicing Equipment, NEC 210-63: Need a receptacle outlet
within 25 ft. for the of HVAC equipment in attics and crawl spaces.
- Receptacles
in Hallways, NEC 210-52(h): For hallways 10 ft. or more in length,
at
least one receptacle outlet is required.
- Ampere
rating of receptacles .
- See
receptacles and GFCI-receptacles sketch
.
- Electrical
boxes .
- Electrical
boxes fill calculations.
|