OVERHEAD SERVICE
CONDUCTORS CLEARANCES
For service conductors that do not exceed
600 volts...
- Above walkway: 10 ft.
NEC 230-24(b).
- Above driveway: 12 ft.
15 ft. min. if voltage exceeds 300. 230-24(b).
- Above
roadway & pools:
18 ft. 230-24(b), 680-8, exception.
Clearance Above Roof
- Pitch of less than 4-in-12:
Min. 8 ft. clearance. 230-24(a).
- Pitch of more than 4-in-12:
Min. 3 ft. 230-24(a), exception #2.
Where voltage between conductors does not exceed 300 volts.
|