GROUNDING ELECTRODE CONDUCTOR
- Grounding
Electrode Conductor (GEC), NEC 100-A:
Is the conductor used to connect the Grounding Electrode to the
equipment grounding conductor, to the grounded conductor, or to both,
of
the circuit at the service equipment or at the source of separately derived
system. It is required to be copper, aluminum or copper-clad aluminum. ,
- Sizing
of the Grounding Electrode Conductor (GEC): Based on the size of service
feeders. The GEC size is determined per NEC, Table
250-66. See exception #1 for Grounded Systems.
- GEC
Materials, NEC 250-62: Copper, aluminum or
copper-clad aluminum.
- A
#6 or larger grounding conductor that is securely-fastened to the building
construction, free from exposure to physical damage, may
be run along the surface of the building without metal covering or protection.
Otherwise, installation required in a rigid metal conduit, EMT, rigid
nonmetallic conduit or IMC is
required. 250-64(b).
- Metal
Underground Gas Piping, NEC 250-52(a):
Not to be used as the Grounding Electrode.
- "UFER" Electrode
System (One of the Grounding Electrode Systems [GES]), NEC 250-50(c):
An electrode encased by at least 2" of concrete, located within
and near the bottom of a concrete foundation or footing, that is direct
contact with earth, consisting of at least 20 ft. of one or more
bare steel reinforcing bar or rod at least 1/2" in diam. (#4 rebar),
or consisting of at least 20 ft. of bare copper conductor not smaller
than #4. ,
,
- Grounding using metal conduit.
|