1. General Lighting & Receptacle Loads. NEC 220-3(b) Not including open porches, garages, unused or unfinished spaces not adaptable for future use |
3 VA x __________ (sq. ft.) |
1 | . | |
2. Small Appliance Branch
Circuits. NEC 220-16(a) Al least 2 small appliances branch circuits must be included. NEC 210-11(c)1 |
1500 VA x __________ (min. 2) |
2 | . | |
3. Laundry Branch Circuit(s).
NEC 220-16(b), 220-4(c) At least 1 laundry branch circuit must be included. |
1500 VA x __________ (min. 1) |
3 | . | |
4. Add lines 1, 2 and 3 | 4 | . | ||
5. _____________ - 3000=__________________________ VA (line 4) |
5 | . | ||
6. _______________________ x 0.35=_________________ VA (line 5) |
6 | . | ||
7. TOTAL General Lighting
and Receptacle Load 3000 + _____________________ = __________________ VA (line 6) |
7 | . | ||
8. Fastened-In-Place Appliances. NEC 220-17 Use nameplate rating. Do not include electric ranges, clothes dryers, space-heating or A/C equipment |
||||
|
8 | . | ||
9. Clothes Dryers. NEC 220-18 If not present >>skip. Otherwise, use 5000 watts or nameplate rating whichever is larger (no derating required for up to 4 dryers) |
9 | . | ||
10. Ranges, ovens, Cooktops and other cooking appliances over 1750 watts. NEC 220-19. If not present >>skip. Otherwise, use Table 220-19 along with notes | 10 | . | ||
11. Heating or Air Conditioning. NEC 220-19.
|
11 | . | ||
12. Largest motor (only one). NEC 220-14, 430-24 Multiply the largest motor volt-amps x 25% _____________________x 0.25= ___________ enter on line 12 (largest motor v-a) |
12 | . | ||
13. TOTAL Volt-Amp Demand Load: Add lines 7 through 12 | 13 | . | ||
14. MIN. Amperes for Service (Total v-a / voltage)= (Line 13) / 240V (voltage= 240, for 120/240V service)= _____________ / 240V= ________________ AMPS
|
14 | . | ||
15. MIN. Size for Service Conductors/Feeders. NEC 240-6(a). Use next STANDARD size fuse or breaker . | 15 | . | ||
16. Size of Service and/or Feeder Conductors. Use 310-15(b) for the service conductors up to 400A. Rating > 400 amps; Use Table 310-16 . MIN. SIZE of CONDUCTORS= |
16 | . | ||
17. Size of Neutral Conductor. NEC 220-22
|
17 | . | ||
20. Size of Grounding Electrode Conductor (GEC). NEC, Table 250-94 . MIN. SIZE of GEC= | 18 |
. |
See an example
calculation for this sizing method |