OPTIONAL METHOD-SINGLE FAMILY DWELLING
ELECTRICAL SIZING CALCULATIONS
1. General Lighting & Receptacle Loads. NEC 220-3(b)
Not including open porches, garages, unused or unfinished spaces not adaptable for future use
3 VA x
 __________
(sq. ft.)
1 .
2. Small Appliance Branch Circuits. NEC 220-30(b)1
Al least 2 small appliances branch circuits must be included. NEC 210-11(c)1
1500 VA x
 __________
(min. 2)
2 .
3. Laundry Branch Circuit(s). NEC 220-30(b)1
At least 1 laundry branch circuit must be included. 
1500 VA x
__________
(min. 1)
3 .
4. Appliances. NEC 220-30(b)3 & 4:
Use nameplate rating of ALL appliances fastened-in-place, permenantly connected, or connected to a specific circuit), ranges, ovens, cooktops, motors and clothes dryers. Convert nameplate ampereage rating to volts-amperes by multiplying the amperage by voltage. Do not include any heating or air-condionting equipment in this section.


water heater:___________________ (in VA's)

compactor:    ____________________

dishwasher: ____________________

garbage disposal: ________________

range: _________________________

_____________:_________________

4 .
5. Demand Factors. NEC 220-30(b) for the total of lines 1 through 4.

[(Total of lines 1-4) - 10,000] x 40% + 10,000


[_____________ - 10,000] x 0.4 = ____________ + 10,000=
5 .
6. Heating and/or Air Conditioning Loads. NEC 220-30(c)
Use nameplate rating(s) in volt-amperess for all applicable systems in lines a through e below.
a. Air conditioning and cooling system(s), including heat pump compressors and supplemental heating, unless the controller prevents the compressor and supplemental heating from operating at the same time.

______________________
_ x 100% = ______________________

 
6(a)= __________________
b. Electrical space heating equipment, if less than 4 separately controlled units: 

______________________
_ x 65% = ______________________


6(b)= __________________
c. Electrical thermal storage and other heating systems where usual load is expected to be continuous at full nameplate value: Systems qualifying under this selection shall not be figured under any other selction in 220-30(c): 

______________________
_ x 100% = ______________________


6(c)= __________________
d. Central electric spce heating equipment, including integral supplemental heating in heat pumps where the controller prevents the compressor and supplemental heating from operating at the same time.
 
______________________
_ x 65% = ______________________


6(d)= __________________
e. Electrical space heating equipment, if 4 or more separately controlled units: 

______________________
_ x 40% = ______________________


6(e)= __________________
7. TOTAL Volt-Ampere Demand Load:

Largest VA rating from lines 6(a) through 6(e) + Line 5

_________________________ + _______________________
7 .
8. MIN. Amperes for Service (Total v-a / voltage)=

(Line 7) / 240V (voltage= 240, for 120/240V service)=

_____________ / 240V=  ________________ AMPS


8 .
9. MIN. Size for Service Conductors/Feeders. NEC 240-6(a). Use next STANDARD size fuse or breaker. Min. size shall be 100 amps. 9 .
10. Size of Service and/or Feeder Conductors
Use section 310-15(b) for the service conductors up to 400A.
Rating > 400 amps; Use Table 310-16 . MIN. SIZE of CONDUCTORS=
10 .
11. Size of Neutral Conductor. NEC 220-22
  1. NEC section 310-15(b) allows neutral to be smaller than the ungrounded (hot) conductors, provided 215-2, 220-22 and 230-42 are met. 
  2. Size the neutral by finding the max. unbalanced load
  3. Neutral cannot be smaller than the required grounding electrode conductor specified in Table 250-94 . MIN. SIZE of NEUTRAL CONDUCTOR=
11 .
12. Size of Grounding Electrode Conductor (GEC). NEC, Table 250-94 . MIN. SIZE of GEC= 12 .


v-a= volts-amperes=watts

To find amperage of 1-phase appliances when HP (horse power) and voltage is known; use Table 430-148

Information to gather before staring load calcs.